Product Features
Standard Features
Installs directly onto a 4” or a 6 riser or top mounted spill container
Minimum shut-off height is 2” from the tank top
2.35” of float height adjustment
Full flow to shut-off point, cushioned closure eliminates shock
Integral pressure relief
Optional test mechanism
Construction Details
- Remote adaptor: ductile iron, powder coated
- Body: nickel plated aluminum
- Drop tube coupler: stainless steel
- Lower pipe nipple: e-coated steel
- Shaft, linkage and hardware: stainless steel
Code Compliance
ULC-S661-10 listed, NFPA 30, 30A, UFC, IFC, PEI /RP200, PEI/RP 600, and Florida DEP EQ-895
Optional Criteria
Minimum 5 PSI flow requirements
Maximum operating pressure is 100 PSI
Maximum viscosity of 300 centistokes
A tight fill connection is required for the valve to operate
Use methanol-compatible threaded pipe (not supplied: drop tube nor upper pipe)
The estimated flow rate for the 2” model is 230 GPM at 10 PSI pressure drop. The estimated flow rate for the 3” model is 560 GPM at 10 PSI pressure drop
Product Ordering Instructions
Figure
|
|
Suffix
|
|
Size
|
|
Tank Opening
|
|
Description
|
Weight (lbs)
|
9095AM
|
3200 AV
|
2”
|
|
4”
|
Pressure fill OPV with remote fill top
|
14.1 | |||
9095AM
|
3300 AV
|
3”
|
|
6”
|
Pressure fill OPV with remote fill top
|
30 |